M.UNION Verified Suppliers in China, provides quality made in China products and certified China manufacturers. All China manufacturers in manufacturer-union.com are certificated by manufacturer union.
Recommended Enterprises
You Are Here: About Company » Products Categories » Low-Voltage Electrical Product » EKL1-63B 10KA B Type Residual Current Circuit Breaker
EKL1-63B 10KA B Type Residual Current Circuit Breaker
Technical Data
Electrical Features
Mode:EKL1-63B 10KA B | Electromagnetic |
Type(wave form of the earth leakage sensed) | B |
Rated current In | 25,40,63A |
Poles | 4P |
Rated voltage Ue | 4P 415V~ |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated residual operation current(I△n) | 30mA |
Rated residual making and breaking capacity (I△m) | 500(In=2540A) 630(In=63A) |
Short-circuit current Inc= I△c | 10,000A |
SCPD fuse |
![]() |
Break time under I△n | ≤0.1s |
Rated impulse withstand voltage(1.5/50) Uimp | 4000V |
Dielectric test voltage at ind.Freq. for 1min | 2.5kV |
Electrical life | 2,000 Cycles |
Mechanical life | 4,000 Cycles |
Installation
Contact position indicator | Yes |
Protection degree | IP20 |
Ambient temperature(with daily average≤35℃) | -5℃~+40℃ |
Storage temperature | -25℃~+70℃ |
Terminal connection type | Cable/Pin-type busbar/U-type busbar |
Terminal size top/bottom for cable | 25mm2 18-3AWG |
Terminal size top/bottom for busbar | 25mm2 18-3AWG |
Tightening torque | 2.5Nm 22In-lbs |
Mounting | On DIN rail EN60715(35mm) by means of fast clip device |
Connection | From top and bottom |
Tripping Current Range
Lagging Angle | I△n>0.01A | I△n≤0.01A |
0° | 0.35I△n≤I△≤1.4I△n | 0.35I△n≤I△≤2I△n |
90° | 0.25I△n≤I△≤1.4I△n | 0.25I△n≤I△≤2I△n |
135° | 0.11I△n≤I△≤1.4I△n | 0.11I△n≤I△≤2I△n |
etectable wave form | Pulsating direct current sensitive | Surge current proof |
B class Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz,pulsating direct residual currents and for smooth direct residual currents,whether applied suddenly or increasing slowly. |
They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency. |
RCCB’s surge capacity. |
Circuit Diagram
Overall and Installation Dimension(mm)
Changan Group Co.,Ltd
Add:No.288 Wei 17th Road, Yueqing Economic Development Zone, Yueqing, Wenzhou, Zhejiang Province, P.R.China
Tel:+ 0086-577-62763666 62760888
Fax:+0086-577-62774090
Website:https://www.changanelectric.com
Email:sales@changangroup.com.cn