M.UNION Verified Suppliers in China, provides quality made in China products and certified China manufacturers. All China manufacturers in manufacturer-union.com are certificated by manufacturer union.
Recommended Enterprises
You Are Here: About Company » Products Categories » Low-Voltage Electrical Product » EKM1-63S 4.5KA Miniature Circuit Breaker
EKM1-63S 4.5KA Miniature Circuit Breaker
Technical Data
Rated current In | 1,2,3,4,5,6,8,10,13,16,20,25,32,40,50,63A |
Poles | 1P, 1P+N, 2P, 3P, 3P+N,4P |
Rated voltage Ue | 240/415V |
Insulation voltage Ui | 500V |
Rated frequency | 50/60Hz |
Rated breaking capacity | 4,500A |
Energy limiting class | 3 |
Rated impulse withstand voltage(1.5/50) Uimp | 4,000V |
Dielectric test voltage at ind. Freq. for 1 min | 2kV |
Pollution degree | 2 |
Thermo-magnetic release characteristic | B,C,D |
Electrical life | 4,000 Cycles |
Mechanical life | 10,000 Cycles |
Contact position indicator | Yes |
Protection degree | IP20 |
Reference temperature for setting of thermal element | 30℃ |
Ambient temperature (with daily average≤35℃) | -5℃~+40℃ |
Storage temperature | -25℃~+70℃ |
Terminal connection type | Cable/Pin-type busbar |
Terminal size top/bottom for cable | 25mm2 18-3AWG |
Terminal size top/bottom for busbar | 25mm2 18-3AWG |
Tightening torque | 2.5Nm 22In-Ibs |
Mounting | On DIN rail EN 60715 (35mm) by means of fast clip device |
Connection | From top and bottom |
Auxiliary contact | EKM1S-OF |
Alarm contact | EKM1S-FB |
Shunt release | EKM1S-MX |
Over/Under voltage release | EKM1S-MV+MN |
Based on the Tripping Characteristics, MCB are available in“B”,“C”and“D”curve to suit different types of applications.
“B”Curve for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits) Short circuit release is set to (3-5)In.
“C”Curve for protection of electrical circuits with equipment that cause surge current (inductive loads and motor circuits) Short circuit release is set to (5-10)In.
“D”Curve for protection of electrical circuits with cause high inrush current ,typically 12-15 times the thermal rated current (transformes, x-ray machines etc,)Short circuit release is set to (10-20)In.
Changan Group Co.,Ltd
Add:No.288 Wei 17th Road, Yueqing Economic Development Zone, Yueqing, Wenzhou, Zhejiang Province, P.R.China
Tel:+ 0086-577-62763666 62760888
Fax:+0086-577-62774090
Website:https://www.changanelectric.com
Email:sales@changangroup.com.cn